TxIsoBlock-HRT

HART® Temperature Transmitter

Temperature transmitter TxIsoBlock-HRT combines the proven quality of HART® certification with the robustness of NOVUS devices. The transmitter is compatible with HART® certified devices and it has electrical isolation between input and output, supporting voltage surges up to 1.5 kVrms. Its great differential is the total configuration through the two 4-20 mA current loop wires, which means more features for device configuration and monitoring.

 

By using a worldwide known protocol with more than 40 million field instruments supporting HART® technology, NOVUS’s temperature transmitter TxIsoBlock-HRT enables the use of standard HART® configuration and supervision software that provides flexibility to users.

 

– Input Type: J, K, T, N, R, S, B, E, Pt100, Pt1000, NTC and 0-50 mV
– Accuracy Typical:
  Pt1000 / mV: 0.07 % span
  Pt100: 0.08 % span
  T/C: 0.07 % span ±1 °C (1.8 °F)
  NTC: 0.2 °C (0.36 °F)

– Maximum:
  Pt1000 / mV: 0.15 % span
  Pt100: 0.15 % span
  T/C: 0.15 % span ±1 °C (1.8 °F)
  NTC: 0.45 °C (0.81 °F)”

– Output Type: 4-20 mA

– Output Resolution: 0.25 µA

– Thermal Drift: < 0.05 % / 25 °C (77 °F)

– Isolation Input-Output: 1.5 kVrms

– Electric Protection: Reverse Polarity

– HART® Version: HART V7, compatible with HART V5

– Configuration Interface: Through TxConfig-HRT adapter or HART®
certified HandHeld

– Configuration Software: TxConfig II

– Approvals / Regulations: CE, NAMUR NE43, RoHS, Reach, HART®

– Electromagnetic Compatibility
  CISPR 11
  EN 61000-4-2
  EN 61000-4-3
  EN 61000-4-4
  EN 61000-4-5
  EN 61000-4-6
  EN 61000-4-8

– Operating Conditions: -40 to 85 °C (-40 to 185 °F) | 0 to 90% RH

– Power Supply: 4-20 mA Loop Powered (8.5 – 36 Vdc)

– Enclosure: PA66

– Format / Mounting: Head Mount

 

 

TxIsoRail-HRT

HART® Temperature Transmitter

Temperature transmitter TxIsoRail-HRT combines the proven quality of HART® certification with the robustness of NOVUS devices. The transmitter is compatible with HART® certified devices and it has electrical isolation between input and output, supporting voltage surges up to 1.5 kVrms. Its great differential is the total configuration through the two 4-20 mA current loop wires, which means more features for device configuration and monitoring.

 

By using a worldwide known protocol with more than 40 million field instruments supporting HART® technology, NOVUS’s temperature transmitter TxIsoRail-HRT enables the use of standard HART® configuration and supervision software that provides flexibility to users.

– Input Type: J, K, T, N, R, S, B, E, Pt100, Pt1000, NTC and 0-50 mV

– Accuracy Typical:
  Pt1000 / mV: 0.07 % span
  Pt100: 0.08 % span
  T/C: 0.07 % span ±1 °C (1.8 °F)
  NTC: 0.2 °C (0.36 °F)

– Maximum:
  Pt1000 / mV: 0.15 % span
  Pt100: 0.15 % span
  T/C: 0.15 % span ±1 °C (1.8 °F)
  NTC: 0.45 °C (0.81 °F)

– Output Type: 4-20 mA

– Output Resolution: 0.25 µA

– Thermal Drift: < 0.05 % / 25 °C (77 °F)

– Isolation Input-Output: 1.5 kVrms

– Electric Protection: Reverse Polarity

– HART® Version: HART V7, compatible with HART V5

– Configuration Interface: Through TxConfig-HRT adapter or HART® certified HandHeld

– Configuration Software: TxConfigII

– Approvals / Regulations: CE, NAMUR NE43, RoHS, Reach, HART®

– Electromagnetic Compatibility:
  CISPR 11
  EN 61000-4-2
  EN 61000-4-3
  EN 61000-4-4
  EN 61000-4-5
  EN 61000-4-6
  EN 61000-4-8

– Operating Conditions: -40 to 85 °C (-40 to 185 °F) 0 to 90% RH

– Power Supply: 4-20 mA Loop Powered (8.5 – 36 Vdc)

– Dimensions: 114 mm x 99.5 mm (4.49 in x 3.91 in)

– Enclosure: ABS UL94-HB

– Format / Mounting: 35 mm (TS35) DIN Rail.

Tx Iso Hart